Conduit / Raceway Fill
Chapter 3 - Wiring Methods / Materials · Article / reference: Chapter 9, Table 1; Tables 4 and 5
Key Requirements
Raceway fill is determined from the actual conductor areas and the permitted percentage of the raceway internal area.
Chapter 9 Table 1 permits 53% for one conductor, 31% for two conductors, and 40% for over two conductors in the general case.
Use the conductor dimensions/areas for the actual insulation and conductor type.
Mixed conductor sizes require summing the individual conductor areas.
Exceptions / Watch Items
Nipples not over 24 in. have a 60% fill allowance under the applicable Chapter 9 note.
Annex C tables are useful only for the exact raceway and conductor combination shown.
Common Field Gotchas
Do not use ampacity conductor diameter assumptions for fill.
Count grounding and bonding conductors when they are installed in the raceway.