Conduit / Raceway Fill

Chapter 3 - Wiring Methods / Materials · Article / reference: Chapter 9, Table 1; Tables 4 and 5

Key Requirements

  • Raceway fill is determined from the actual conductor areas and the permitted percentage of the raceway internal area.
  • Chapter 9 Table 1 permits 53% for one conductor, 31% for two conductors, and 40% for over two conductors in the general case.
  • Use the conductor dimensions/areas for the actual insulation and conductor type.
  • Mixed conductor sizes require summing the individual conductor areas.

Exceptions / Watch Items

  • Nipples not over 24 in. have a 60% fill allowance under the applicable Chapter 9 note.
  • Annex C tables are useful only for the exact raceway and conductor combination shown.

Common Field Gotchas