Article 250 - Grounding / Bonding

6
Grounding vs Bonding
Ref: Article 250 · grounding, bonding, EGC, GEC

Grounding connects the system or equipment to earth; bonding establishes electrical continuity and an effective ground-fault current path. Exception/watch: Services, separately derived systems, and special occupancies each have...

Other Metal Piping Bonding
Ref: 250.104(B) · gas pipe, bonding, metal piping

Other metal piping systems likely to become energized shall be bonded as required by 250.104(B). Exception/watch: CSST systems can have manufacturer instructions and fuel-gas-code bonding requirements beyond the electrical rule.

Metal Water Pipe / Electrode
Ref: 250.50; 250.52(A)(1); 250.53(D); 250.104(A) · water pipe, GEC, bonding, electrode

If a metal underground water pipe qualifies as a grounding electrode, it shall be included in the grounding electrode system. Exception/watch: Electrode qualification depends on direct contact with earth for the required length and...

Grounding Electrode System
Ref: 250.50; 250.52; 250.53 · grounding electrode, ufer, ground rod

All grounding electrodes described in 250.52(A)(1) through (A)(7) that are present at a building or structure shall be bonded together to form the grounding electrode system. Exception/watch: Rod, pipe, plate, concrete-encased,...

Service Bonding
Ref: 250.24; 250.28 · service, main bonding jumper, neutral bond

The grounded service conductor shall be connected to the grounding electrode system as required by 250.24. Exception/watch: Existing installations and separately derived systems have separate provisions.

Separately Derived Systems
Ref: 250.30 · transformer, SDS, bonding

Separately derived alternating-current systems shall be grounded and bonded in accordance with 250.30 where required. Exception/watch: Some systems are not separately derived because of a direct electrical connection to another source...

Chapter 2 - Wiring and Protection

10
Conductor Ampacity Basics
Ref: 310.15; Table 310.16 · ampacity, 310.16, derating, termination

Conductors shall have ampacity sufficient for the load after required adjustment and correction factors are applied. Exception/watch: Specific equipment articles, small-conductor rules, dwelling service/feeders, motors, HVAC, and...

Continuous Loads
Ref: 100; 210.19(A); 215.2; 210.20(A) · continuous load, 125 percent, 3 hours

A continuous load is a load where the maximum current is expected to continue for 3 hours or more. Exception/watch: Listed assemblies rated for 100% operation can have specific provisions.

AFCI Field Reference
Ref: 210.12 · AFCI, 210.12, dwelling, branch circuit

AFCI protection shall be provided for the branch circuits and locations identified by the adopted edition of 210.12. Exception/watch: Check the adopted edition and local amendments for exceptions and extension rules.

Equipment Grounding Conductor Sizing
Ref: 250.122; Table 250.122 · EGC, 250.122, ground wire

Equipment grounding conductors shall be sized in accordance with 250.122 and the rating or setting of the circuit overcurrent device, subject to the article rules. Exception/watch: Specific equipment articles can require different or...

Motor Branch-Circuit Basics
Ref: 430.6; 430.22; 430.32; 430.52 · motor, FLC, overload, OCPD

Motor full-load current used for conductor and branch-circuit short-circuit/ground-fault protection calculations is generally determined from the Article 430 tables as directed by 430.6. Exception/watch: Nameplate current is used...

Transformer Secondary Conductors
Ref: 240.21(C) · transformer secondary, tap conductor, 240.21

Transformer secondary conductors shall be protected in accordance with one of the permitted 240.21(C) rule paths. Exception/watch: Outdoor secondary conductors and supervised industrial installations have separate provisions.

Circuit Directories / Identification
Ref: 408.4(A) · panel, directory, circuit identification

Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. Exception/watch: Existing directories should be corrected when circuit modifications make them inaccurate.

Dedicated Equipment Space
Ref: 110.26(E) · dedicated space, panelboard, foreign systems

Indoor switchboards, switchgear, panelboards, and motor control centers shall have dedicated equipment space as required by 110.26(E). Exception/watch: Suspended ceilings with removable panels are not considered structural ceilings...

Voltage Drop Design Reference
Ref: 210.19(A) Informational Note; 215.2 Informational Note · voltage drop, feeder, branch circuit

Voltage drop recommendations appear in informational notes and are design considerations rather than blanket mandatory ampacity requirements. Exception/watch: Sensitive loads and long runs can justify larger conductors even when...

Grounding Electrode Conductor Splicing
Ref: 250.64(C) · GEC, splice, irreversible compression, exothermic

A grounding electrode conductor shall be installed in one continuous length without a splice or joint except as permitted by 250.64(C). Exception/watch: The rule contains specific allowances for taps and busbar arrangements.

Chapter 3 - Wiring Methods / Materials

2
Box Fill
Ref: 314.16 · box fill, device yoke, EGC, clamps

Boxes shall be of sufficient size to provide free space for all enclosed conductors. Exception/watch: Check listed box volume markings and applicable raceway-body rules.

Conduit / Raceway Fill
Ref: Chapter 9, Table 1; Tables 4 and 5 · conduit, raceway, fill, EMT, THHN

Raceway fill is determined from the actual conductor areas and the permitted percentage of the raceway internal area. Exception/watch: Nipples not over 24 in. have a 60% fill allowance under the applicable Chapter 9 note.

Dwelling / Device Protection

1
GFCI Field Reference
Ref: 210.8 · GFCI, 210.8, receptacle, dwelling

GFCI protection shall be provided in the locations and for the outlets/equipment covered by the adopted edition of 210.8. Exception/watch: Specific listed exceptions and accessibility provisions must be checked in the adopted edition.

Equipment / Special Equipment

2
Motor Disconnecting Means
Ref: 430.102; 430.109 · motor disconnect, within sight, controller

Disconnecting means shall be provided for the controller and motor as required by 430.102. Exception/watch: Lockable disconnect provisions can affect the within-sight requirement under applicable exceptions.

Transformer Protection Basics
Ref: 450.3 · transformer, 450.3, primary, secondary

Transformer overcurrent protection shall be provided in accordance with 450.3 and the applicable table. Exception/watch: Supervised locations and transformers over or under specific impedance/voltage conditions can use different table...

General Field Reference

3
Termination Temperature Limits
Ref: 110.14(C) · termination, 75C, 60C, 90C

Conductor ampacity shall be based on the temperature rating of the termination as required by 110.14(C). Exception/watch: Listed equipment identified for other conductor temperature ratings is used in accordance with its listing.

Electrical Working Space
Ref: 110.26 · working space, clearance, 110.26

Working space about electrical equipment shall be provided and maintained to permit ready and safe operation and maintenance. Exception/watch: Special installations and existing conditions can involve other rules, but field...

Arc-Flash / Equipment Marking Reminder
Ref: 110.16 · arc flash, warning label, marking

Electrical equipment identified by 110.16 shall be field or factory marked to warn qualified persons of potential electric arc-flash hazards. Exception/watch: The NEC warning-marking rule is not a substitute for an NFPA 70E arc-flash...

Language rule: cards preserve shall / shall not / exception character where it matters and summarize field use without trying to become the entire code book.