
Indexed GIES field reference for article lookup, bookmarks, and local notes. Full NEC text is not bundled.
This section is an index and note layer only. Use your licensed 2020 NFPA 70 / NEC book, NFPA LiNK access, or AHJ-published adopted code source for exact enforceable text. Do not treat this page as the full code.
81 indexed itemsLocal notes enabledFull text not stored
Short GIES field cards are grouped directly in the code tab below. Use the full cards when you need the detailed bullet list, exceptions, and gotchas.
Open Full Quick Card LibraryLegacy Common CardsGrounding connects the system or equipment to earth; bonding establishes electrical continuity and an effective ground-fault current path. Exception/watch: Services,...
Other metal piping systems likely to become energized shall be bonded as required by 250.104(B). Exception/watch: CSST systems can have manufacturer instructions and...
If a metal underground water pipe qualifies as a grounding electrode, it shall be included in the grounding electrode system. Exception/watch: Electrode qualification depends...
All grounding electrodes described in 250.52(A)(1) through (A)(7) that are present at a building or structure shall be bonded together to form the grounding electrode system....
The grounded service conductor shall be connected to the grounding electrode system as required by 250.24. Exception/watch: Existing installations and separately derived...
Separately derived alternating-current systems shall be grounded and bonded in accordance with 250.30 where required. Exception/watch: Some systems are not separately derived...
Conductors shall have ampacity sufficient for the load after required adjustment and correction factors are applied. Exception/watch: Specific equipment articles,...
A continuous load is a load where the maximum current is expected to continue for 3 hours or more. Exception/watch: Listed assemblies rated for 100% operation can have...
AFCI protection shall be provided for the branch circuits and locations identified by the adopted edition of 210.12. Exception/watch: Check the adopted edition and local...
Equipment grounding conductors shall be sized in accordance with 250.122 and the rating or setting of the circuit overcurrent device, subject to the article rules....
Motor full-load current used for conductor and branch-circuit short-circuit/ground-fault protection calculations is generally determined from the Article 430 tables as...
Transformer secondary conductors shall be protected in accordance with one of the permitted 240.21(C) rule paths. Exception/watch: Outdoor secondary conductors and supervised...
Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. Exception/watch: Existing directories should be...
Indoor switchboards, switchgear, panelboards, and motor control centers shall have dedicated equipment space as required by 110.26(E). Exception/watch: Suspended ceilings...
Voltage drop recommendations appear in informational notes and are design considerations rather than blanket mandatory ampacity requirements. Exception/watch: Sensitive loads...
A grounding electrode conductor shall be installed in one continuous length without a splice or joint except as permitted by 250.64(C). Exception/watch: The rule contains...
Boxes shall be of sufficient size to provide free space for all enclosed conductors. Exception/watch: Check listed box volume markings and applicable raceway-body rules.
Raceway fill is determined from the actual conductor areas and the permitted percentage of the raceway internal area. Exception/watch: Nipples not over 24 in. have a 60% fill...
GFCI protection shall be provided in the locations and for the outlets/equipment covered by the adopted edition of 210.8. Exception/watch: Specific listed exceptions and...
Disconnecting means shall be provided for the controller and motor as required by 430.102. Exception/watch: Lockable disconnect provisions can affect the within-sight...
Transformer overcurrent protection shall be provided in accordance with 450.3 and the applicable table. Exception/watch: Supervised locations and transformers over or under...
Conductor ampacity shall be based on the temperature rating of the termination as required by 110.14(C). Exception/watch: Listed equipment identified for other conductor...
Working space about electrical equipment shall be provided and maintained to permit ready and safe operation and maintenance. Exception/watch: Special installations and...
Electrical equipment identified by 110.16 shall be field or factory marked to warn qualified persons of potential electric arc-flash hazards. Exception/watch: The NEC...
Purpose, scope, arrangement, enforcement concepts, and how to read the NEC in the field.
Keywords: scope, purpose, enforcement, mandatory, permissive, explanatory
Related:
Primary definitions used across the Code. Start here when a term drives the answer.
Keywords: definitions, qualified person, readily accessible, continuous load, grounded, bonding
Related: 110
General installation requirements, listing/labeling, working space, conductor terminations, equipment markings, and workmanship.
Keywords: working space, listing, labeling, torque, termination, 110.26, equipment space
Related: 100, 250
Grounded conductor identification, white/gray rules, and neutral conductor field identification issues.
Keywords: neutral, grounded conductor, white wire, gray wire, identification
Related: 210, 215, 250
Core branch-circuit rules for outlets, receptacles, required circuits, GFCI/AFCI references, and dwelling/commercial branch work.
Keywords: branch circuit, receptacle, GFCI, AFCI, small appliance, laundry, bathroom, garage, 210.8, 210.12, 210.52
Related: 220, 250, 406
Feeder sizing, ratings, voltage drop informational notes, and feeder identification in service/subpanel work.
Keywords: feeder, subpanel, ampacity, voltage drop, neutral
Related: 220, 225, 230, 250
Load calculations for dwellings, commercial spaces, feeders, and services.
Keywords: load calculation, service calculation, dwelling, demand factor, commercial load
Related: 210, 215, 230
Outside feeders/branch circuits, building disconnect rules, and detached structure feeds.
Keywords: detached garage, outside feeder, building disconnect, overhead, underground
Related: 215, 230, 250
Service conductors, service disconnecting means, service equipment, service entrance rules, and common utility/service work references.
Keywords: service, service disconnect, service equipment, meter, service entrance, 230.71
Related: 225, 250, 408
Breaker/fuse protection rules, standard ratings, tap conductors, conductor protection, and equipment protection.
Keywords: breaker, fuse, OCP, overcurrent, tap conductor, 240.4, 240.6
Related: 310, 408, 430
Surge protective devices and overvoltage protection requirements.
Keywords: surge, SPD, overvoltage
Related: 230, 250, 285
Grounding electrode systems, bonding, equipment grounding conductors, grounded conductors, and service/subpanel grounding logic.
Keywords: grounding, bonding, GEC, EGC, ground rod, water pipe, gas bonding, subpanel, 250.66, 250.122
Related: 100, 110, 200, 230, 680
SPD installation, connection, and application references.
Keywords: surge protective device, SPD, transient voltage
Related: 242, 230, 250
General wiring method rules: protection, securing/support, boxes, raceways, wet locations, and underground basics.
Keywords: wiring method, raceway, cable, support, secure, wet location, underground
Related: 310, 314, 358, 352
Conductor ampacity, insulation types, temperature ratings, and adjustment/correction references.
Keywords: ampacity, conductor, THHN, THWN, temperature, 310.16, derating
Related: 240, 300, 334
Cabinets and enclosures including wire bending and conductor space concerns.
Keywords: cabinet, enclosure, meter socket, wire bending
Related: 314, 408
Box fill, pull boxes, junction boxes, device boxes, conduit bodies, and handholes.
Keywords: box fill, junction box, pull box, device box, conduit body, 314.16
Related: 300, 370, Chapter 9
AC cable rules and limitations.
Keywords: AC cable, armored cable
Related: 300, 330
MC cable installation rules, uses, support, and limitations.
Keywords: MC cable, metal clad, support
Related: 300, 320, 334
NM-B rules for residential and light commercial contexts, protection, securing, and permitted uses.
Keywords: NM-B, Romex, nonmetallic sheathed cable, dwelling, support
Related: 300, 310, 320
SE/USE cable applications for service and feeder work.
Keywords: SE cable, USE cable, service entrance
Related: 230, 310, 334
IMC raceway uses, installation, support, and fittings.
Keywords: IMC, intermediate metal conduit
Related: 344, 358
Rigid metal conduit installation rules.
Keywords: RMC, rigid conduit, galvanized rigid
Related: 342, 358
FMC rules for flexibility, support, and permitted uses.
Keywords: flex, FMC, greenfield
Related: 350, 356
Liquidtight flex rules for wet/damp locations and equipment connections.
Keywords: liquidtight, LFMC, sealtite, wet location
Related: 348, 356
PVC conduit installation, expansion, underground, sunlight, and support references.
Keywords: PVC, schedule 40, schedule 80, underground, expansion fitting
Related: 300, 355, 358
LFNC rules for wet/damp locations and equipment whip-style use.
Keywords: LFNC, nonmetallic liquidtight, whip
Related: 350, 352
EMT installation, support, fittings, bends, corrosion protection, and common commercial raceway work.
Keywords: EMT, thinwall, conduit, support, strap, coupling, connector
Related: 300, 344, 352
ENT installation and permitted/limited uses.
Keywords: ENT, smurf tube
Related: 352, 358
Wireway fill, conductor count, splices, and industrial/commercial use.
Keywords: wireway, gutter, auxiliary gutter, fill
Related: 366, 378
Cable tray installation, support, and permitted cable types.
Keywords: cable tray, tray cable, industrial
Related: 300, 336
Flexible cord rules, uses not permitted, strain relief, and temporary equipment connection issues.
Keywords: cord, flexible cord, SO cord, extension cord
Related: 590, 422
Switch installation, switching of grounded conductors, snap switches, and enclosure requirements.
Keywords: switch, snap switch, disconnect switch
Related: 406, 430
Receptacle ratings, replacement rules, tamper resistance, weather resistance, grounding-type devices, and device applications.
Keywords: receptacle, outlet, NEMA, tamper resistant, weather resistant, WR, TR
Related: 210, 250, 422
Panelboards, switchboards, switchgear, circuit directories, unused openings, and panel equipment rules.
Keywords: panelboard, switchgear, switchboard, directory, breaker, unused opening
Related: 110, 230, 240
Lighting fixture installation, supports, clearance, LED/retrofit considerations, and luminaire rules.
Keywords: lighting, luminaire, fixture, lampholder, LED
Related: 411, 410
Low-voltage lighting systems, power supplies, and installation rules.
Keywords: low voltage lighting, landscape lighting, driver
Related: 410, 725
Appliance branch circuits, disconnecting means, nameplate ratings, and appliance installation references.
Keywords: appliance, dishwasher, water heater, disconnect
Related: 210, 422, 440
Baseboard, space heat, and fixed heating equipment circuits/controls.
Keywords: baseboard heat, space heater, electric heat
Related: 210, 422
Motor conductor sizing, overloads, short-circuit protection, disconnects, and controller rules.
Keywords: motor, overload, MCC, starter, disconnect, VFD
Related: 240, 440, 460
A/C and refrigeration disconnects, conductor/OCP sizing, MCA/MOCP labels, and HVAC equipment rules.
Keywords: HVAC, air conditioner, MCA, MOCP, condenser, disconnect
Related: 430, 422
Generator installation, marking, disconnecting means, and wiring references.
Keywords: generator, genset, standby, portable generator
Related: 250, 700, 701, 702
Transformer installation, ventilation, overcurrent protection, and vault references.
Keywords: transformer, dry type, vault, primary, secondary
Related: 240, 250
Battery installations, ventilation, disconnects, and energy storage tie-ins.
Keywords: battery, UPS battery, stationary battery
Related: 645, 706
Medium-voltage equipment rules and references.
Keywords: medium voltage, over 1000V, MV
Related: 110, 240
Hazardous location classification system and general Class/Division/Zone structure.
Keywords: hazardous location, classified, Class I, Division, Zone
Related: 501, 502, 503, 504, 505, 506
Flammable gas/vapor Class I wiring methods and equipment.
Keywords: Class I, explosionproof, sealoff, gas vapor
Related: 500, 504, 505
Combustible dust Class II wiring methods and equipment.
Keywords: Class II, dust, combustible dust
Related: 500, 506
Commercial garage classification and wiring concerns.
Keywords: commercial garage, repair garage, vehicle
Related: 500, 514
Gas station/fuel dispenser wiring and classified location references.
Keywords: gas station, fuel dispenser, service station
Related: 500, 501
Healthcare essential electrical systems, patient care spaces, grounding, receptacles, and branch requirements.
Keywords: healthcare, hospital, patient care, essential electrical system, 517
Related: 700, 701
Assembly occupancy wiring and equipment references.
Keywords: assembly, church, auditorium, occupancy
Related: 520, 525
Stage, theater, performance, and studio wiring references.
Keywords: theater, stage, performance, studio
Related: 518, 530
Event power, temporary wiring, and outdoor public event rules.
Keywords: fair, carnival, temporary event, festival
Related: 590
Agricultural building wiring, equipotential planes, corrosive/dusty/wet conditions.
Keywords: agricultural, barn, livestock, equipotential plane
Related: 250, 300
Dock and marina power, GFCI/GFPE, shore power, corrosion/wet location concerns.
Keywords: marina, dock, boat, shore power
Related: 250, 682
Sign circuits, disconnecting means, and outline lighting references.
Keywords: sign, neon, outline lighting
Related: 410
Elevator/lift electrical equipment, disconnects, and coordination references.
Keywords: elevator, lift, escalator, disconnect
Related: 430, 645
EV charging equipment, branch circuits, load management, GFCI references, and installation rules.
Keywords: EV, EVSE, charger, electric vehicle
Related: 210, 220, 250
Welder circuits, conductor sizing, duty cycle, and OCP references.
Keywords: welder, welding, duty cycle
Related: 240, 310
IT equipment rooms, UPS/data equipment, disconnects, and fire/smoke conditions.
Keywords: IT room, server room, data center, UPS
Related: 480, 700
Pipe organ electrical references.
Keywords: pipe organ
Related:
X-ray equipment branch circuit and control references.
Keywords: x-ray, medical equipment
Related: 517
Pool bonding, GFCI, equipment grounding, wet niche fixtures, fountains, and related installations.
Keywords: pool, hot tub, spa, fountain, bonding, equipotential
Related: 250, 555
Electrical work near bodies of water not otherwise covered.
Keywords: pond, lake, water, dock
Related: 555, 680
PV circuits, disconnects, rapid shutdown, labeling, grounding, and interconnection references.
Keywords: solar, PV, photovoltaic, rapid shutdown
Related: 705, 706
Fire pump power supply, disconnects, reliability, and emergency/standby coordination.
Keywords: fire pump, pump controller
Related: 700, 701
Emergency systems, wiring separation, transfer equipment, and life-safety power references.
Keywords: emergency system, life safety, generator, ATS
Related: 517, 701, 702
Legally required standby systems, transfer equipment, and standby wiring.
Keywords: legally required standby, standby, ATS
Related: 700, 702
Optional standby generators and transfer equipment for residential/commercial standby systems.
Keywords: optional standby, generator, transfer switch
Related: 445, 700, 701
Interconnection of power production sources such as PV with premises wiring.
Keywords: interconnection, backfeed, line side tap, solar
Related: 690, 706
Battery/energy storage systems, disconnects, location, and equipment references.
Keywords: ESS, battery storage, energy storage, inverter
Related: 480, 690, 705
Critical operations power systems for facilities requiring hardened power reliability.
Keywords: critical operations, COPS, mission critical
Related: 700, 701
Control wiring, power-limited circuits, Class 2/3, and separation from power conductors.
Keywords: Class 2, low voltage, control wire, power limited, thermostat
Related: 760, 800
Fire alarm circuit classifications, wiring methods, power-limited/non-power-limited circuits.
Keywords: fire alarm, FACP, notification, initiating, NAC
Related: 725, 770, 800
General communications circuit wiring and separation references.
Keywords: communications, low voltage, data, telecom
Related: 725, 805
Communications circuits and cabling references.
Keywords: communications circuit, phone, data
Related: 800
Coaxial cable/CATV grounding and bonding references.
Keywords: coax, CATV, antenna
Related: 800, 830
Network-powered broadband communications wiring references.
Keywords: broadband, network powered
Related: 800, 820
Conduit fill, conductor properties, resistance/reactance, and table-based calculations. Use exact NEC tables for final values.
Keywords: conduit fill, wire fill, table 1, table 4, table 5, resistance, reactance
Related: 300, 310, 314
Annex fill tables for raceway/conductor combinations. Informational; verify against adopted NEC usage.
Keywords: Annex C, fill table, conduit fill, EMT fill, PVC fill
Related: Chapter 9, 300